Availability: In stock

Exd IIC Gb, Exe IIC Gb, Extb IIIC Db Non-armoured ATEX IECEx Approved

from £15.13 excl. VAT

501/414 Cable Gland Details

Application

Outdoor or indoor use.

For use with non-armoured elastomer and plastic insulated cables installed in conduit.

Features

Provides a cable retention seal onto the cables outer sheath.

When used in increased safety applications, this cable gland may be used with braided cable where the braid and the cables outer sheath pass into the enclosure. The braid must be suitably terminated into the enclosure.

Provides female running coupler for cable gland or conduit entry.

Materials & Finishes

The 501/414 cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.

Hawke 501/414 OS M20-M20
Part Number: HBG41420OS
£15.13

Low stock

Hawke 501/414 O M20-M20
Part Number: HBG41420O
£15.13

Low stock

Hawke 501/414 A M20-M20
Part Number: HBG41420A
£15.13

36 in stock

Hawke 501/414 B M25-M25
Part Number: HBG41425B
£24.26

19 in stock

Hawke 501/414 C M32-M32
Part Number: HBG41432C
£44.12

Low stock

ManufacturerHawke
Brass

Technical Data

Exd IIC Gb, Exe IIC Gb, Extb IIIC Db

Certificate No's

Baseefa06ATEX0056X and IECEx BAS 06.0013X.

Suitable for use in:

Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.

Construction and Test Standards:

IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.

Ingress Protection:

IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.

Deluge Protection to:

DTS01

Operating Temperature Range:

-60°C to +100°C