ACT20X-2HDI-2SDO-RNC-S
Weidmuller ACT20X-2HDI-2SDO-RNO-S

ACT20X-2HDI-2SDO-RNC-S Weidmuller

Part Number: 8965380000

Availability: Enquire about stock

ACT20X, EX signal isolating converter, 2-channel version, NC

£120.97 excl. VAT

ACT20X-2HDI-2SDO-RNC-S Details

Ex isolating switch amplifiers for Namur sensors, 2 channels

2-channel isolating switch amplifiers in 22.5 mm width with an external power supply,

to transmit and isolate Namur sensor signals from Ex zones 0,1, 2 into the safe 

zone. 

On the output side there is a potential-free relay contact per channel with opening function

and a common alarm contact ("a" contact) for status/error messages.

The component can be configured using standard FDT/DTM software.

Supply voltage19.2 – 31.2 V DC
Type of connectionScrew connection, Removable terminal block
NAMUR supply8 V DC / 8 mA
Power consumption≤ 3 W (2 channels)
Protection degreeIP 20
Humidity0...95 % (no condensation)
ManufacturerWeidmuller
Product TypeNAMUR disconnect-switch amplifier, with relay output

Ex isolating switch amplifiers for Namur sensors, 2 channels

2-channel isolating switch amplifiers in 22.5 mm width with an external power supply,

to transmit and isolate Namur sensor signals from Ex zones 0,1, 2 into the safe

zone.

On the output side there is a potential-free relay contact per channel with opening function

and a common alarm contact ("a" contact) for status/error messages.

The component can be configured using standard FDT/DTM software.

Add-on housing for TS35 DIN rail installation

Dimensions: L/W/H 119.2/ 22.5/ 113.6

screw connection / nominal cross-section 2.5 mm2Protection degree: IP20   Input /channel NAMUR sensor according to EN 60947                                     8 VDC / 8 mA sensor power supply 

                                    0.5 kHz input frequency                                     wire-break detectionOutput Ex/ channel     Relay 1 NC contact

                                     250 VAC / 30 VDC @ 2A safe zone                                    32 VAC @ 5 kHz 32 VDC @ 1 A zone 2Alarm output relay 1 NO contact 

                                     250 VAC / 30 VDC @ 2A safe zone                                     32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2

Auxiliary power                   19...31.2 VDCPower loss approx. 3 WAmbient

temperature range -20 °C to +60 °C

Secure isolation                   EN 61010, 4-way isolation up to 2.6 kV AC/DC of all circuits against each other

Working voltage                     300 V AC/DC at overvoltage category II and pollution degree 2

Approvals cULus, ATEX IECEX, FM

ATEX marking II 3 G ExnA nC IIC T4

ATEX characteristic data U0 = 10, 6 V DC

                                      I0  = 12 mA DC

                                      P0 = 32 W

Type                                                           ACT20X-HDI-2SDO-2RNC-S