Your Harsh & Hazardous Area
Solutions Company

Sales and advice call or email +44 (0)1925 852745
sales@cablesystems.co.uk
Opening times: Mon - Thur 8am-5pm / Fri 8am - 3pm

  1. Trade Account
  2. Videos
  3. Downloads
  4. Contact
  5. News
  6. Basket
  7. Login
  8. Register
You are here
I.S Signal Converters
ACT20X-HDI-SDO-RNO-S
Weidmuller ACT20X-2HDI-2SDO-RNO-S

ACT20X-HDI-SDO-RNO-S Weidmuller

Part Number: 8965340000

Availability: 5 in stock

ACT20X, EX signal isolating converter, 1-channel version, NO

£101.84 excl. VAT

ACT20X-HDI-SDO-RNO-S Details

Ex isolating switch amplifiers for Namur sensors

1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,

to transmit and isolate Namur sensor signals from Ex zones 0,1,2 into the safe zone. 

On the output side there is a potential-free relay contact with closing function and an alarm contact for

status/error messages.

The component can be configured using standard FDT/DTM software.

Supply voltage19.2 – 31.2 V DC
Type of connectionScrew connection, Removable terminal block
NAMUR supply8 V DC / 8 mA
Power consumption≤ 3 W (2 channels)
Protection degreeIP 20
Humidity0...95 % (no condensation)
ManufacturerWeidmuller
Product TypeNAMUR disconnect-switch amplifier, with relay output

Ex isolating switch amplifiers for Namur sensors

1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,

to transmit and isolate Namur sensor signals from Ex zones 0,1,2 into the safe zone. 

On the output side there is a potential-free relay contact with closing function and an alarm contact for

status/error messages.

The component can be configured using standard FDT/DTM software.

Add-on housing for TS35 DIN rail installation

Dimensions: L/W/H 119.2/ 22.5/ 113.6

Screw connection/ nominal cross-section 2.5 mm2Protection degree: IP20   

Input                      NAMUR sensor according to EN 60947 

                                    8 VDC / 8 mA sensor power supply 

                                    0 to 5 kHz input frequency 

                                    wire-break detection

Output                                            Relay 1 NO contact

                                     250 VAC / 30 VDC @ 2A safe zone

                                    32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2

Alarm output relay 1 NO contact 

                                     250 VAC / 30 VDC @ 2A safe zone

                                     32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2

Auxiliary power                                    19 to 31.2 VDC

Power loss approx. 1.8 W

Ambient

temperature range -20 °C to +60 °C

Secure isolation                 EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each other

Working voltage                   300 V AC/DC at overvoltage category II and pollution degree 2

Approvals cULus, ATEX IECEX, FM 

ATEX marking II 3 G ExnA nC IIC T4 

ATEX characteristic data U0 = 10, 6 V DC

                                      I0  = 12 mA DC

                                      P0 = 32 W

Type                                                           ACT20X-HDI-SDO-RNO-S