CEAG GHG2640025R0001 SAFETY SWITCH

CEAG 80A 3-pole Safety Switch, 2 x M50 cable gland, direct drilled enclosure

  • 80A 3-pole Safety Switch
  • Auxiliary contact: none
  • 2 x M50 cable gland, direct drilled enclosure

Please enter a quantity

Share this product:

CEAG GHG2640025R0001

80A 3-pole Safety Switch

Auxiliary contact: none

2 x M50 cable gland, direct drilled enclosure

CEAG GHG26 EXPLOSION PROTECTED DISCONNECT SWITCHES

CEAG GHG26 disconnect switches from Eaton’s Crouse-Hinds Division are used to control motor, lighting and other circuits, and prevent arcing internal to the enclosed switch from causing ignition of a specific hazardous atmosphere. GHG26 switches are designed for industrial areas such as chemical plants, oil and gas refineries, paint and varnish manufacturing plants, gasoline bulk loading terminals and finishing areas where sturdy, durable enclosures are required.

Ex-safety switches 80 A
Marking accd. to 2014/34/EU II 2 G Ex db e [ia/ib] IIB/IIC T5/T6 Gb / II 2 D Ex tb IIIC T80 °C Db
EC-Type Examination Certificate BVS 15 ATEX E 125 X
IECEx Certificate of Conformity IECEx BVS 15.0103X
Marking accd. to IECEx Ex ed ia IIC T6
Ex tD A21 IP66 T53 °C
Permissible ambient temperature –20 °C up to +40 °C1)
Rated voltage up to max. 690 V
Rated current max. 80 A
Frequency 50/60 Hz
Rated making-/ breaking capacity AC-3
accd. EN 60947-3
Ue 230 V / Ie 80 A
Ue 400 V / Ie 80 A
Ue 500 V / Ie 80 A
Ue 690 V / Ie 63 A
Rated making-/ breaking capacity DC 1/DC 23
accd. EN 60947-3
Ue 60 V / Ie 80 A (1 contact)
Ue 120 V / Ie 80 A (2 contacts in series)
Switch-disconnector for maintenance accd. to IEC 62262-1 Class 1
Back-up fuse up to 400 V AC: 160 A gG
up to 500 V AC: 160 A gG
up to 690 V AC: 125 A gG
Connecting terminals      main contact

auxiliary-/Signal contact

2 x 25 mm2

2 x 4 mm2 (option)

Degree of protection accd. to EN 60529 IP 66
Protection class I
Cable glands/enclosure drilling M25 cable gland see ordering details
M32 cable gland see ordering details
M50 cable gland see ordering details
Option: metal flange with thread
Weight                                        3/4-pole
6-pole
approx. 6.5 kg
approx. 9.0 kg
Enclosure material glass-fibre reinforced polyester
Enclosure colour black
Auxiliary contact (option) 1 x NO making – lagging; breaking – leading
1 x NC making – leading; breaking – lagging
Padlocking facility can be locked in OFF position with 3 commercially available padlocks (Ø max. 6 mm)
1) Other ambient temperatures on request

CEAG 80A Safety Switch Datasheet

Product Enquiry