Hazardous Area Products // Control & Distribution // Control Stations // CEAG Two Gang Control Stations Type GHG 411 82

CEAG Two Gang Control Stations Type GHG 411 82

Moulded plastic for Zone 1, 2, 21 and 22

Clear

Share this product:

GHG 411 82 Double Gang Control Stations

Ex Control Stations for Individual Configuration

CEAG control stations can be combined according to customers‘ specifications. Quick fixing allows up to three CEAG built-in components, such as signal lamps, pushbuttons and switches, to be snapped on a rail in the enclosure. The enclosures consist of low-temperature impact-resistant thermoplastic which fulfils the requirements of EN 60079 and provides a high resistance to chemicals. The well thought out design with low side walls allows optimum cable connection. The components can be snapped out of the enclosure to facilitate cable-entry feeding. Notches in
the mounting rails prevent the built-in components from being twisted out of place.

CEAG‘s optional mounting plates offer a time-saving fixing technique. Coupling pieces link enclosures to each other and prevent them from being twisted out of place. Alternatively,
metal screws and flanges can be used for mounting – the metal flanges also enable external earthing.

The built-in components differ in size. The diverse enclosure types allow variable combinations of these components. Example diagrams of the enclosure types show the placement options for the built-in components with numbers or predefined positions.

Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements.

Reliable control of processes

Even under the most adverse conditions, CEAG control stations can be used and operated reliably. The enclosures consist of low-temperature impact-resistant thermoplastic which fulfils the requirements of EN 60079 and provides a high resistance to chemicals. The well thought out design with low side walls allows optimum cable connection.

Modular design

Quick fixing allows up to three CEAG built-in components, such as signal lamps, pushbuttons and switches, to be snapped on a rail in the enclosure. They can be snapped out of the enclosure to facilitate cable-entry feeding. Notches in the mounting rails prevent the built-in components from being twisted out of place.

Easy to install

Wall mounting can be carried out via easily accessible fixing apertures when the enclosure cover is sealed. CEAG mounting pla tes offer a time-saving fixing tech nique. CEAG control stations feature standard M25 moulded-plastic cable entries with an 10 to 17.5 mm clamping diameter. Coupling pieces link enclosures to each other and prevent them from being twisted out of place. Alternatively, metal screws and flanges can be used for mounting – the metal flanges also enable external earthing. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements.

Features

  • Flat side walls
  • Quick fixing of all built-in components
  • High chemical resistance
  • Different enclosures can be combined
Ex-control stations Type 411 82
Marking accd. to 2014/34/EUII 2 G Ex ed ib m IIC T6
II 2 D Ex tD A21 IP66 T80 °C
EC-Type Examination CertificatePTB 00 ATEX 3117
IECEx Certificate of ConformityIECEx BKI 04.0003
Marking accd. to IECExEx e II T6, Ex e ib IIC T6, Ex ed IIC T6 or Ex ed ib IIC T6
Permissible ambient temperature–20 °C up to +40 °C
–55 °C up to +55 °C (option)
Rated voltage690 V AC
Rated current16 A
Rated making-/rated breaking capacity
accd. EN 60947-5-1
Ex41
AC-15: Ue 250 V / Ie 6 A
Ue 500 V / Ie 4 A
DC-13: Ue 24 V / Ie 6 A
Ue 110 V / Ie 0.5 A
Ex23
AC-15: Ue 230 V / Ie 6 A
Ue 500 V / Ie 4 A
DC-13: Ue 24 V / Ie 2 A
Ue 230 V / Ie 0.5 A
Connecting terminals2 x 2.5 mm2
Protection classI
Degree of protection accd. to EN 60529IP66 (standard)
Cable glands/Gland plates/Enclosure drilling1 x M25 cable gland or 1 x M20 thread with brass flange
Enclosure materialPolyamide
Enclosure colourblack
Type 411 82
Dimensions (L x W x H)125 x 85 x 77.5 mm
Weight (empty)0.35 kg
Type 411 82 with measuring instrument AM 72
MovementMoving ironMoving coil
Marking accd. to 2014/34/EUII G Ex e IIII G Ex ib IIC
AccuracyClass 2.5Class 1.5
Overload range10-fold -25 sec.
25-fold – 4 sec.
50-fold – 1 sec.
10-fold -5 sec.
1) Base enclosure can be rotated after wards (entry from top or down)
Other versions available on request

CEAG GHG 411 Series Control Stations