Speak to a team member +44 (0) 1925 852745

Hawke PL626

Increased Safety Heavy Duty GRP Terminal Enclosure – Increased Safety Exe, IP66/67, Atex/IECEX/EAC/INMETRO/CSA/UL

Cable Systems provide an in-house Design, Assembly & Certification service for this item.

Please contact us with the following information;-

  • Size & Quantity of Terminals
  • Linking / Cross-connecting requirements (if any)
  • Size, Quantity & Position of Cable Entries
Clear

Share this product:

Moulded from Glass Reinforced Polyester with Natural Black Finish. ATEX,IECEx,EAC,CSA,UL Certified.

  • The Ultimate in Robust GRP Construction designed to withstand impact resistance up to 7Nm.
  • GRP construction provides a high degree of resistance to corrosive atmospheres.
  • Corrosion Resistant Stainless Steel Lid Fixing Screws with Nylon Retaining Washers prevents loss of screws during assembly and maintenance.
  • Anti-Static Properties Removes the risk of ignition sources through static induced sparking resistivity
  • Insulation resistance less than 1GΩ.

For Intrinsically Safe Applications, Exe power terminals can be supplied in blue on request. (Note: the enclosure will remain Exe certified).

General
Application
  • Increased Safety Ex II 2 GD
  • Exe IIC Gb
  • Extb IIIC Db.
Ingress Protection
  • IP66
  • IP67
  • DTS01
Material Glass Reinforced Polyester
Operating Temperature Range Celsius -60°C to +75°C
Series PL Series
Certifications and Compliance
ATEX File Number Baseefa06ATEX0117X; Baseefa06ATEX0116U
Certified Listed
  • ATEX
  • IEC
  • EAC
  • INMETRO
  • NEC
Compliance
  • Exe
  • Extb
Hazardous Rating(s)
  • Zone 1
  • Zone 2
  • Zone 21
  • Zone 22
IECEx File Number IECEx BAS 06.0028X; IECEx BAS 06.0027U
Industry Standard(s)
  • IEC/EN 60079-0
  • IEC/EN 60079-7
  • IEC/EN 60079-31.