ICG 653/Universal/L Cable Gland
Hawke ICG 653 UNIVERSAL L Cable Gland

ICG 653/Universal/L Cable Gland Hawke

Availability: Enquire about stock

Exd IIC Gb, Exe II Gb, Extb IIIC Db Armoured ATEX IECEx Approved

from £35.89 excl. VAT

ICG 653/Universal/L Cable Gland Details


Outdoor or indoor use.

For use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables with a lead inner sheath.

For particular use with:-

a) Cables that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers.

b) Cables that exhibit ‘cold flow’ characteristics.

c) Enclosures containing an ignition source in gas group IIC areas or containing an ignition source in a Zone 1 area and exceeding 2 litres in volume.


Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.

Assembly of the cable gland compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure.

The compound chamber may be separated from the cured compound to ensure that the chamber has been effectively filled. If required, external voids can be repaired.

Provides armour clamping, using one clamping arrangement for all armour/braid types.

Provides a seal and an electrical bond on the cables lead inner sheath.

Provides an outer deluge seal to prevent moisture ingress to the cable armour/braid.

Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.

Materials & Finishes

The ICG 653/Universal/L cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard.

Hawke ICG 653 Univ AL M20 Lead
Part Number: HBG653U20AL

Low stock

Hawke ICG 653 Univ BL M25 Lead
Part Number: HBG653U25BL

Low stock

Hawke ICG 653 Univ OL M20 Lead
Part Number: HBG653U20OL

Low stock


Technical Data

Exd IIC Gb, Exe II Gb, Extb IIIC Db

Certificate No's

Baseefa06ATEX0058X and IECEx BAS 06.0015X.

Suitable for use in:

Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.

Construction and Test Standards:

IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.

Ingress Protection:

IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.

Deluge Protection to:


Operating Temperature Range:

-60°C to +80°C

Assembly Instruction Sheet:

AI 301 & AI 336.