Speak to a team member +44 (0) 1925 852745
Home › Harsh & Industrial Products › Flexible Conduit Systems › Kopex PST Pliable Conduit

Kopex PST Pliable Conduit

Low Fire Hazard Pliable Conduit.

Clear

Share this product:

Type PST

Low fire hazard halogen free, low smoke toxicity

  • Pliable (Bend to Shape)
  • Galvanised steel & Kraft Paper core – Low Fire Hazard jacket
  • Temperature range – Static applications: -20ºC to +90ºC
  • IP66 – IP67 rating (with C12 fittings)
  • Medium flexibility and fatigue life

Typical applications

  • Liquid resistant Indoors / Outdoors, light industrial, underground, rail infrastructure, where low smoke & toxicity is a primary concern.

Approvals

  • BSI Kitemark KM-90009
  • Low voltage directive
  • London Underground 1-085
  • NFF16-101 (I1 F1)
Part Code Conduit Size Metric Conduit Size US Trade Coil Length (M) A – Outside Diameter (Mm) B – Inside Diameter C – Static Bend Radius (Mm)
(Mm) (Inches) (Mm)
PST02* 12 5/16” 10/30 14.6 8.3 25
PST03* 16 3/8” 10/30 17.8 11.6 30
PST04* 20 1/2” 10/30 21.0 14.6 35
PST05* 25 3/4” 10/30 27.3 20.4 45
PST06* 32 1” 10/20 34.0 26.7 55
PST07* 40 1 1/4” 10/20 40.4 32.8 70
PST08* 50 1 1/2” 10/20 53.1 45.3 110

Product Enquiry

  • This field is for validation purposes and should be left unchanged.