Speak to a team member +44 (0) 1925 852745
Home › Hazardous Area Products › Power & Control › Safety Switches & Isolators › CEAG GHG2632301R0002 EMERGENCY STOP

CEAG GHG2632301R0002 EMERGENCY STOP

CEAG 40A 3-pole Emergency Stop, 2 x M40 & 1 x M25 cable gland, direct drilled enclosure

  • 40A 3-pole Safety Switch
  • Auxiliary contact: 1NO
  • 2 x M40 & 1 x M25 cable gland, direct drilled enclosure
Product Code: GHG2632301R0002

£660.40 (excl. VAT)

Availability: Can be back ordered, average Lead Time: 4 weeks

Share this product:

CEAG GHG2632301R0002

40A 3-pole Emergency Stop

Auxiliary contact: 1NO

2 x M40 & 1 x M25 cable gland, direct drilled enclosure

CEAG GHG26 EXPLOSION PROTECTED DISCONNECT SWITCHES

CEAG GHG26 disconnect switches from Eaton’s Crouse-Hinds Division are used to control motor, lighting and other circuits, and prevent arcing internal to the enclosed switch from causing ignition of a specific hazardous atmosphere. GHG26 switches are designed for industrial areas such as chemical plants, oil and gas refineries, paint and varnish manufacturing plants, gasoline bulk loading terminals and finishing areas where sturdy, durable enclosures are required.

Ex-safety switches 40 A
Marking accd. to 2014/34/EU II 2 G Ex ed ia IIC T6 / II 2 D Ex tD A21 IP66 T80 °C
EC-Type Examination Certificate PTB 99 ATEX 1161
IECEx Certificate of Conformity BKI 07.0012
Marking accd. to IECEx Ex ed ia IIC T6
Ex tD A21 IP66 T53 °C
Permissible ambient temperature –20 °C up to +40 °C1)
Rated voltage up to max. 690 V
Rated current max. 40 A
Frequency 50/60 Hz
Rated making-/ breaking capacity AC-3
accd. EN 60947-3
Ue 230 V / Ie 40 A
Ue 400 V / Ie 40 A
Ue 500 V / Ie 40 A
Ue 690 V / Ie 32 A
Rated making-/ breaking capacity DC 1/DC 23
accd. EN 60947-3
Ue 60 V / Ie 40 A (1 contact)
Ue 120 V / Ie 40 A (2 contacts in series)
Switch-disconnector for maintenance accd. to IEC 62262-1 Class 1
Back-up fuse up to 400 V AC: 80 A gG
up to 500 V AC: 80 A gG
up to 690 V AC: 63 A gG
Connecting terminals      main contact

auxiliary-/Signal contact

2 x 16 mm2

2 x 4 mm2 (option)

Degree of protection accd. to EN 60529 IP 66
Protection class I
Cable glands/enclosure drilling M25 cable gland see ordering details
M40 cable gland see ordering details
Option: metal flange with thread
Weight                                        3-pole
6-pole
approx. 2.30 kg
approx. 2.75 kg
approx. 6.50 kg
Enclosure material glass-fibre reinforced polyester
Enclosure colour black
Auxiliary contact (option) 1 x NO making – lagging; breaking – leading
1 x NC (only 6-pole version) making – leading; breaking – lagging
Padlocking facility can be locked in OFF position with 3 commercially available padlocks (Ø max. 6 mm)
1) Other ambient temperatures on request

CEAG 40A Emergency Stop Datasheet

Product Enquiry

  • This field is for validation purposes and should be left unchanged.