| Twilight switch with Ex-e enclosure |
| Marking accd. to 2014/34/EU |
D II 2 G Ex Ex d e IIC T5 Gb |
EC-Type Examination Certificate terminal box GHG 721:
GHG 74: |
BVS 13 ATEX E 013 X
BVS 12 ATEX E 118 X |
| EC-Type Examination Certificate twilight switch |
PTB 06 ATEX 1017 X |
| Permissible ambient temperature |
‐40°C to +55°C |
IECEx Certificate of Conformity terminal box GHG 721:
GHG 74: |
IECEx BVS 13.0031X
IECEx BVS 12.0071X |
| Marking accd. to IECEx |
Ex d e IIC T5 Gb |
| Rated voltage |
105 ‐ 305 V 50/60 Hz |
| Rated current |
max. 10 A |
| Protection class |
I |
| Rated switching capacity |
1800 VA |
| Light sensitivity |
4 – 11 lux, 7 – 12 lux, 10 – 15 lux, adjustable, lower value “ON”, upper value “OFF” |
| Degree of protection accd. to EN 60529 |
IP66 |
| Enclosure material |
glass-fibre reinforced polyester (GHG 721 00) or stainless steel (GHG 744 21) |
| Enclosure colour |
black or polished |