501/453/RAC Cable Gland (Stainless Steel)
Hawke 453 RAC Cable Gland

501/453/RAC Cable Gland (Stainless Steel) Hawke

Availability: In stock

Exd IIC Gb, Exe IIC Gb, Extb IIIC Db Armoured ATEX IECEx Approved

from £52.61 excl. VAT

501/453/RAC Cable Gland (Stainless Steel) Details

Application

Outdoor or indoor use.

For use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables.

Features

Provides armour clamping using one clamping arrangement for all armour/braid types.

Provides a seal on the cables inner sheath.

Deluge protection option available, contact Hawke Technical Sales for details.

Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.

Materials & Finishes

The 501/453/RAC cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.

Hawke 501/453 RAC OS M20 Stainless Steel
Part Number: HSG453R20OS
£52.61

Low stock

Hawke 501/453 RAC O M20 Stainless Steel
Part Number: HSG453R20O
£52.61

9 in stock

Hawke 501/453 RAC A M20 Stainless Steel
Part Number: HSG453R20A
£62.03

2 in stock

Hawke 501/453 RAC B M25 Stainless Steel
Part Number: HSG453R25B
£93.74

Low stock

ManufacturerHawke
316 Stainless Steel

Technical Data

Exd IIC Gb, Exe IIC Gb, Extb IIIC Db

Certificate No's

Baseefa06ATEX0056X and IECEx BAS 06.0013X.

Suitable for use in:

Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.

Construction and Test Standards:

IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.

Ingress Protection:

IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.

Deluge Protection to:

DTS01 (Deluge seal optional).

Operating Temperature Range:

-60°C to +80°C

Assembly Instruction Sheet:

AI 302.