Speak to a team member +44 (0) 1925 852745
Home › Hazardous Area Products › Heaters & Thermostats › Air Warmers › EXHEAT FCR Hazardous Area Convector Heaters

EXHEAT FCR Hazardous Area Convector Heaters

Heavy duty folded steel construction and finned stainless steel elements give the FCR range an exceptionally long life. The FCR range is certified for use in hazardous areas where the atmosphere is classified as a Zone 1 or 2 (IIA, IIB, IIC) gas group.

Can be back ordered

Please enter a quantity

Share this product:

Heavy duty folded steel construction and finned stainless steel elements give the FCR range an exceptionally long life. The FCR range is certified for use in hazardous areas where the atmosphere is classified as a Zone 1 or 2 (IIA, IIB, IIC) gas group.

Features

  • Certified to ATEX and IECEx standards
  • Certified weatherproof protected to IP67
  • Small footprint, occupying less floor space
  • Sloped top, preventing objects being placed on the grill
  • Floor or wall mounting
  • Integral terminal enclosure
  • Suitable for ambient temperatures from -60°C to +40°C
  • Incoloy 800 finned elements for long life
  • Grey gloss, powder coated, sheet steel construction
  • Optional built on room temperature control thermostat
  • 2 × M20 (temporary plugged) cable entry provided as standard

Typical Applications

  • Aircraft hangars
  • Fuel servicing areas
  • Chemical plants
  • Offshore installations
  • Battery stores
  • Gas installations
  • Container heating
  • Storage areas
  • Frost protection
GENERAL
CertificationATEX / IECEx    II 2 G
Ex e IIC T2 to T3 Gb Zone 1 and 2 (IP67)
CU TR (EAC). CSA approval from Q1 for Zones and Divisions
EnclosureHeavy duty powder coated mild steel
ElementsFinned heating elements, comprising high quality 80/20 nickel chrome resistance wire, compacted in magnesium oxide insulating powder and encased in an Incoloy 800 sheath
ControlsIf required, the heaters can be controlled from the EXHEAT range of remote mounted thermostats available for use in hazardous areas
MountingWall or floor mounting via brackets / feet supplied
Voltage1 phase: 110 to 120V and 230 to 254V
3 phase: 380 to 440V, subject to design parameters
RatingStandard heating ratings 1kW, 2kW and 3kW

EXHEAT FCR Hazardous Area Convector Heaters Datasheet

Product Enquiry

  • This field is for validation purposes and should be left unchanged.