Hawke 501/414 Cable Gland

Flameproof Exd / Increased Safety Exe / Dust Extb single compression seal conduit cable gland

Clear

Share this product:

The 501/414 cable gland provides a seal on the outer cable sheath and is intended for use on non-armoured elastomer and plastic insulated cables installed in conduit. The cable gland is dual certified Exd and Exe and is suitable for installation in Zone 1 (21) and Zone 2 (22) hazardous areas.

  • Provides a cable retention seal onto the cables outer sheath.
  • When used in increased safety applications, this cable gland may be used with braided cable where the braid and the cables outer sheath pass into the enclosure.
  • The braid must be suitably terminated into the enclosure.
  • Provides female running coupler for cable gland or conduit entry.

Ordering Format [ Gland Type / Size / Male Thread / Female Thread / Material / Options]; Example: 501/414/ C/ M32/ Brass; Example with alternative seal option: 501/414 / C / 1 1¼” NPT /Brass / S

General
ApplicationSuitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Ingress Protection
  • IP66
  • IP67
  • IP68
  • Deluge Protected to DTS01
MaterialBrass (standard); Nickel Plated Brass; 316 Stainless Steel or Aluminium; Brass NPT entries are nickel plated as standard
Operating Temparature Range Celcius-60°C to +100°C
SeriesGroup II, Dual Certified, Hazardous Area Cable Glands
Type
  • Exdb
  • Exeb
  • Extb
Certifications and Compliance
ATEX File NumberBaseefa06ATEX0056X
Certified Listed
  • IEC/EN 60079-0
  • IEC/EN 60079-1
  • IEC/EN 60079-7
  • IEC/EN 60079-31
Hazardous Rating(s)
  • Exd IIC Gb
  • Exe IIC Gb
  • Extb IIIC Db
IECEx File NumberIECEx BAS 06.0013X
IP Rating
  • IP66
  • IP67
  • IP68
Industry Standard(s)
  • IEC/EN 60079-0
  • IEC/EN 60079-1
  • IEC/EN 60079-7
  • IEC/EN 60079-31
Nema Rating4X

501/414 Cable Gland Datasheet